Reclamation - All Types

4RSHPA RECLAMATION SYSTEM
(for R-11, 12, 22, 113, 114, 123, 134a, 500, 502)

reclamation system
Reclamation System with 12,000 pound capacity tank

The 4RSHPA system is intended for use as a commercial reclamation unit. Through the use of distillation, separation and filtration processes, the 4RSHPA equipment will clean refrigerants to ARI 700-96 specifications of purity.

The 4RSHPA system has two main components, a Condensing Module and a Distillation Module, assembled on tubular steel frames with casters. The two modules connect with a flexible hose set and power cords. Two high volume refrigerant recovery tanks are recommended to complete this reclamation circuit: one dirty refrigerant recovery tank to feed liquid to the distillation process and one refrigerant recovery tank to receive the condensed reclaimed refrigerant product.

STORAGE TANKS OF ANY SIZE MADE TO ORDER

Electrical
Vapor Recovery
  Reclamation Rate
 
460 - 3 Phase R - 11
6.0 #/min.
R - 11
5.5 #/min.
380 - 3 Phase R - 12 20.0 #/min. R - 12 11.5 #/min.
50 or 60 HZ R - 22 24.0 #/min. R - 22 16.0 #/min.
  R - 113 4.6 #/min. R - 113 3.4 #/min.
Dimensions R - 114 12.5 #/min. R - 114 10.5 #/min.
48" Wide R - 123 6.3 #/min. R - 123 5.4 #/min.
88" Long R - 134a 19.0 #/min. R - 134a 11.5 #/min.
74" High R - 500 20.0 #/min. R - 500 11.0 #/min.
  R - 502 24.8 #/min. R - 502 16.5 #/min.
Weight        
Each module - 1650#        
         
Refrigerant Flow Rates
       
Liquid - All refrigerant @
500 #/min. recovery rate
ALL REFRIGERANTS PROCESSED TO ARI 700 SPECIFICATIONS